Troubleshooting
57
Powerware
®
5140 User’s Guide www.powerware.com
CHAPTER 9
TROUBLESHOOTING
This section explains:
Self-test diagnostic
Site wiring fault
UPS alarms and conditions
How to silence an alarm
Service and support
Initiating the Self-Test
Press and hold the button for three seconds to initiate the self-test.
During the test, the LEDs illuminate as various parts of the UPS are
checked.If the UPS finds a problem,the
indicator illuminates and
the audible alarm beeps.
NOTE The self-test cannot beperformed while the UPS isinBatterymode.
Site Wiring Fault
The Site Wiring Fault alarm is disabled by default and is only needed for
installations with a grounded-neutral electrical system. You can enable
the alarm throughthe System Setup menu on the front panel (see
page 42).
The Site Wiring Fault alarm detects a ground wire connection that does
not exist or reversed line and neutral wires in the line receptacle. If the
condition is detected during startup, the UPS does not supply power to
your equipment. If the condition is detected during Normal mode, the
UPS alarm beeps and the
indicator flashes. Have a qualified
electrician correct the wiring fault.