Installation
25
Powerware
®
5140 User’s Guide www.powerware.com
8. Continue to the following section, “Installing Optional
Equipment,” if you are installing a REPO switch, option
modules, or a power distribution unit (PDU).
Otherwise, continue to “UPS Startup” on page 27.
Installing Optional Equipment
This section describes the UPS options that should be installed before
starting up the UPS:
Remote Emergency Power-Off switch
Option modules
Power Distribution Unit
Remote Emergency Power-Off
WARNING
Onlyqualifiedservice personnel (suchasa licensedelectrician)shouldperform the
REPOinstallation.Risk ofelectrical shock.
The Powerware 5140 includes a REPO port that allows power to be
switched off at the UPS output receptacles from a customer-supplied
switch in a remote location.
The REPO feature shuts downthe protected equipment immediately and
does not follow the orderly shutdown procedure initiated by any power
management software. The REPO feature also shuts down all devices
that are operating on battery power. When the REPO switch is
re-opened, the UPS does not return the equipment to battery power
until manually restarted.
CAUTION
The REPOswitch must bewiredin accordance with NEC (NFPA70, Article 725)
standardsor national andlocalwiring regulations.
The REPOshutdown circuitmustmeet therequirementsof anNEC Class2 circuit
or IEC-950 SecondaryExtra LowVoltage (SELV)circuit andbe separated fromany
hazardousvoltagecircuitsor conductorsby reinforced insulation.
The REPOshutdown circuitmustshort theREPO terminalsand disconnect theAC
inputsource.