Front Panel Menus
41
Powerware
®
5140 User’s Guide www.powerware.com
Comm (Communications) Setup
Use this option to set up the UPS for serial communication. Select Serial
Port 1 or Serial Port 2 and thenselect values for the following options:
Baud rate -select 1200, 2400, 4800, 9600, or 19200
Data bits - select 7 or 8
Stopbits - select 1 or 2
Parity - select Odd, Even, None, Mark, or Space
Assigned Segs - select the individual load segment to assign or disable
that segment for the selected serial port (see Figure 25).
Select Serial Port 1 or Serial Port 2.
Then select the Assigned Segs option.
This example shows that Serial Port 1
controls Load Segment 3.
Scroll down and select a load segment
to assign or disable the load segments
for the specified serial port.
Figure 25. Assigning Load Segments
NOTE Allload segmentsare assigned toboth serialports byfactory-default.If you
are using the LanSafe III/FailSafe III power management software, theloadsegments
mustbe carefullyassigned toprevent theunintentionalshutdownof specificload
segments.