Operation
33
Powerware
®
5140 User’s Guide www.powerware.com
Starting the UPS on Battery
NOTE Before using thisfeature,the UPS musthavebeen powered byutility power
at leastonce and thebatteriesmust becompletely charged.
NOTE The UPS doesnot auto-detect theinput frequencywhenstarting onbattery;
the default isthe lastfrequencyusedbythe UPS.
This feature allows you to start the UPS without utility power.
To tur n o n
the UPS without using utility power, press and hold the On
button for
five seconds.
The UPS supplies power to your equipment and goes into Battery mode.
When the UPS starts on battery, it does not conduct a self-test to
conserve battery power.
Maintenance Bypass
Battery power is not available while on bypass; however, utility power
continues to be passively filtered by the UPS.
To switch the UPS to Maintenance Bypass mode:
1. Turn the Bypass switch on the UPS rear panel to the BYPASS
position (see Figure 23).
The
indicator illuminates and the UPS beeps every three
seconds. The UPS is now powering your equipment directly
from utility power.
Figure 23. TheUPS Bypass Switch