Battery Maintenance
47
Powerware
®
5140 User’s Guide www.powerware.com
CHAPTER 7
BATTERY MAINTENANCE
This section explains how to:
Care for the UPS and batteries
Replace the batteries
Test new batteries
Recycle used batteries
UPS and Battery Care
Forthe best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system witha vacuum cleaner.
Forfull battery life, keep the UPS at an ambient temperature of
25°C (77°F).
Storing the UPS and Batteries
If you store the UPS fora long period,recharge the battery every
12 months by connecting the UPS to utility power. The batteries charge
to 90% capacity in approximately 4 hours. However, it is recommended
that the batteries charge for 24 hours after long storage.
When to Replace Batteries
The batteries should be replaced within 30 to 60 days if the
indicator flashes and the LCD displays Battery Low.
To verify that the batteries need to be replaced, conduct a self-test by
pressing the
button. If the indicator continues to flash, contact
your service representative to order new battery trays.