Strany 1 - 164201300 Rev. G

Installation and OperationManualUninterruptible PowerSupply10 kVA -- 20 kVA25 kVA -- 40 kVA164201300 Rev. G9330

Strany 2

xPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 8. E v e n t s --- A c t i v e 12 --- 6...

Strany 3 - Table of Contents

8-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.2 Using the LCD Screen and PushbuttonsThe LCD screen on the Co

Strany 4 - Section II Operation

8-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3 Using the Main MenuThe UPS main menu allows you to display d

Strany 5

8-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.2 System Event ScreensSelect EVENTS from the Main menu to di

Strany 6

8-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.3 System Meter ScreensSelect METERS from the Main menu to di

Strany 7

8-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The Bypass screen shows the phase-to-neutral voltage, and freque

Strany 8 - List of Figures

8-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The Output Current Screen displays a real-time bar graph of the

Strany 9

8-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.4 Setup Menu ScreensSelect SETUP from the Main menu to displ

Strany 10 - 164201300 REV. G 061502

8-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select DATE &TIME from the System Setup menu to display the

Strany 11 - List of Tables

8-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select SERIAL PORTS from the System Setup menu to display the S

Strany 12

8-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select VERSIONS from the System Setup menu to display the Versi

Strany 13 - Introduction

xiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502List of TablesTa b l e 4 --- 1 . R e m o t e E P O W i r e Te r m i

Strany 14 - System C onfigurations

8-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.4 System Controls ScreenSelect CONTROLS from the Main menu sc

Strany 15 - Using This Manual

8-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502SYSTEM CONTROLSCHARGERBYPASS PPU ONNORMALMAINTENANCE BYPASSBYPA

Strany 16

8-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.4.1 Charger Controls ScreenSelect CHARGER from the System Con

Strany 17 - Safety Considerations

8-- 15Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.5 Unit Shutdown ScreenThe Unit Shutdown screen appears when t

Strany 18 - Getting Help

8-- 16Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.6 Reading the Status IndicatorsThefivesymbolsontheleftsideoft

Strany 19 - Installation

9-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502UPS Operating Instructions9.1 OperationThe following procedures

Strany 20

9-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212. O bserve the following messages appear sequentially on the P

Strany 21 - Getting Started

9-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.4 Starting the Power Processing UnitTo start the Power Process

Strany 22

9-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.5 Cold Starting the UPSTo start the UPS system when commercial

Strany 23

9-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213. O bserve the following messages appear sequentially on the P

Strany 24

xiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 25

9-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.7 Transfer from Bypass to Normal ModeTo transfer the critical

Strany 26

9-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.10 Transfer from Normal to Bypass Mode with UPSShutdown1. Tran

Strany 27 - Installing the UPS System

9-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.13 Options Cabinet Maintenance Bypass TransferTo transfer the

Strany 28 - 2.2 UPS Cabinet Installation

9-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.16 Using the REMOTE EMERGENCY POWER OFFSwitchAn UPS Emergency

Strany 29

9-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 30 - REAR VIEW

10--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Using Features10.1 GeneralThe many standard features of your UPS

Strany 31 - Cabinet from the Pallet

10--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150210.4 Optional Remote Monitor PanelAs an option, you can install

Strany 32

10--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The RMP contains a local horn and the following backlit status i

Strany 33

10--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 34

11- -1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Responding to System Events11.1 GeneralWhen the UPS system is r

Strany 35 - CAUTION:

xiiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502IntroductionPowerware 9330 UPS true double conversion online powe

Strany 36

11- -2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150211.4 System Event MessagesWhen a system event occurs, a message

Strany 37

11- -3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornCheck Inverter 1 4 1 H

Strany 38

11- -4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornInput Phase R o tation

Strany 39

11- -5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornRectifier Under Voltag

Strany 40 - (Non–Permanent Mounting)

11- -6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage Horn Phone Relay Log IndicationABS: Battery DCUV

Strany 41 - (Permanent Mounting)

11- -7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage IndicationLogRelayPhoneHornCalling Phone #2 2 No

Strany 42

11- -8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage IndicationLogRelayPhoneHornSBM IO 2 Not Reportin

Strany 43

11- -9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502STATUSMessage Horn Phone Relay Log IndicationAlarm Lamp No No 1

Strany 44

11- -10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502COMMANDSMessage Horn Phone Relay Log IndicationBypass Mode No

Strany 45

12--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Communications12.1 DescriptionThis chapter describes the serial

Strany 46

xivPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502UPSCABINETBATTERYCABINETOPTIONSCABINETTypical Powerware 9330 (25 k

Strany 47

12--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502321547698TXDRXDDSRRETURNDTRCTSRTSNOT USEDSERIAL PORT (DB--9)NOT

Strany 48

12--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212.5 Terminal ModeIn Terminal Mode, the user can request the fol

Strany 49

12--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 3 . M a i n S c r e e n --- U P S O n B a t

Strany 50

12--5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---5. System ControlsFigure 12 ---6. Load Off

Strany 51

12--6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 7 . E v e n t s --- H i s t o r yF i g u r e

Strany 52

12--7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12 ---9. Input MeterFigure 12---10. Output Meter

Strany 53

12--8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---11. Bypass MeterFigure 12---12. Output Current (Load

Strany 54 - 2.5 Initial Startup

12--9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---13. SetupFigure 12---14. Contrast Adjust

Strany 55 - 2.6.1 Installation Checklist

12--10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---15. Date and Time SetupFigure 12---16. Serial Port

Strany 56

12--11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12 ---17. Versions

Strany 57

xvPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· Parallel System with one to four UPS modules with remote battery

Strany 58 - 3.3 Battery Installation

12--12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212.5.2 Event History LogThis key sequence prints the entire Eve

Strany 59

12--13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Inverter Version 0.97Machine Control Version 0.99Comm Server Ve

Strany 60

12--14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 61 - 3.4 Connecting Batteries

13--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Remote Notification13.1 DescriptionRemote Notification provides

Strany 62 - THIS SECTION

13--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.2 Remote Notification FeaturesRemote Notification provides th

Strany 63

13--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.3 Description of OperationThe Remote Notification option perf

Strany 64

13--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· The UPS logs a successful notify to the event log when the rem

Strany 65 - Power Off (EPO) Control

13--5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.4 Hardware RequirementsThe following hardware components are

Strany 66 - BOTTOM ENCL OSURE

13--6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.5 Configuring the ModemThe modem must be programmed with the

Strany 67

13--7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027. To program a group four number, key in [A], [T], [&], [Z]

Strany 68

xviPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· Chapter 8 -- Using the Control Panel -- describes the controls a

Strany 69 - Monitor Panel

13--8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027. To program a group four number, key in [A], [T], [&], [Z]

Strany 70

13--9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.6.1 Default EventsThe default messages sent are listed in the

Strany 71

13--10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 72

14--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Maintaining the UPS System14.1 GeneralThe components inside the

Strany 73 - Operation

14--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Observe these precautions when working on or around batteries:·

Strany 74

14--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214.3 Performing Preventive MaintenanceThe UPS system requires ve

Strany 75 - Understanding UPS

14--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214.4 Maintenance TrainingA basic training course, available from

Strany 76

15--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Product Specificat i ons15.1 Model NumbersThe UPS systems are ho

Strany 77 - 6.2 UPS Modes

15--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150215.3 UPS System OutputDC Filtering Ripple voltage less than 0.5%

Strany 78 - NORMAL MODE

15--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150215.4 Environmental SpecificationsOperating Temperature 0to40˚C w

Strany 79

xviiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Safety ConsiderationsThe UPS cabinet is designed for industrial o

Strany 80 - BYPASS MODE

15--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 81

A---1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Appendix A --- Customer InformationThe information in this appen

Strany 82 - HIGH EFFICIENCY MODE

DESCRIPTION:DATE:DRAWING NO:1of17SHEET:REVISION:FNOTE:Callout letterandmap to drawing #164201300---6,,,111501ABCD164201300---1POWER WIRING INSTALLATIO

Strany 83 - BATTERY MODE

DESCRIPTION:DATE:DRAWING NO:2of17SHEET:REVISION:ENOTE:Callout letterandmap to drawing #164201300---6,,,071501ABCD164201300---1POWER WIRING INSTALLATIO

Strany 84

DESCRIPTION:DATE:DRAWING NO:3of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABPOWER WIRING INSTALLATION NOTES16420130

Strany 85 - TEST MODE

DESCRIPTION:DATE:DRAWING NO:4of17SHEET:REVISION:ENOTE:Callout letterandmap to drawing #164201300---6,,,071501164201300---1POWER WIRING INSTALLATION NO

Strany 86 - 6.3 Functional Description

DESCRIPTION:DATE:DRAWING NO:5of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABCD164201300---1POWER WIRING INSTALLATIO

Strany 87

DESCRIPTION:DATE:DRAWING NO:6of17SHEET:REVISION:GNOTE:Callout letterandmap to drawing #164201300---6,,,061502ABCD164201300---1POWER WIRING INSTALLATIO

Strany 88

DESCRIPTION:DATE:DRAWING NO:7of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABPOWER WIRING INSTALLATION NOTES16420130

Strany 89 - Operational Controls

DESCRIPTION:DATE:DRAWING NO:8of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001164201300---1POWER WIRING INSTALLATION NO

Strany 90

xviiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502For More InformationThis manual describes how to install and ope

Strany 91

DESCRIPTION:DATE:DRAWING NO:9of17SHEET:REVISION:F111501NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INSTAL

Strany 92 - 7.3 UPS Standard Features

DESCRIPTION:DATE:DRAWING NO:10 of 17SHEET:REVISION:F111501NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INS

Strany 93 - 7.4 Options and Accessories

DESCRIPTION:DATE:DRAWING NO:11 of 17SHEET:REVISION:D053001NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INS

Strany 94 - 7.4.5 Parallel Cabinet

DESCRIPTION:DATE:DRAWING NO:12 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 3Powerware 9330 (10 kVA--40 kVA) Install

Strany 95 - 7.4.6 Communications

DESCRIPTION:DATE:DRAWING NO:13 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 4Powerware 9330 (10 kVA--40 kVA) Install

Strany 96 - 7.5 Safety Considerations

DESCRIPTION:DATE:DRAWING NO:14 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 5Powerware 9330 (10 kVA--40 kVA) Install

Strany 97

DESCRIPTION:DATE:DRAWING NO:15 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 6Powerware 9330 (10 kVA--40 kVA) Install

Strany 98

DESCRIPTION:DATE:DRAWING NO:16 of 17SHEET:REVISION:F111501164201300---1POWER WIRING INSTALLATION NOTESA --- 1 7Powerware 9330 (10 kVA--40 kVA) Install

Strany 99 - Using the Control Panel

DESCRIPTION:DATE:DRAWING NO:17 of 17SHEET:REVISION:D053001164201300---1POWER WIRING INSTALLATION NOTESA --- 1 8Powerware 9330 (10 kVA--40 kVA) Install

Strany 100

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G1of5051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 1 9Powerware 9330 (10 kVA--40 kVA

Strany 101 - 8.3 Using the Main Menu

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Section IInstallation

Strany 102 - 8.3.2 System Event Screens

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G2of5061502CUSTOMER INTERFACE WIRINGINSTALLATION NOTESCSB CUSTOMER INTERFACERELAY #2 NCRELAY #2 RETURNRELA

Strany 103 - 8.3.3 System Meter Screens

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G3of5061502CUSTOMER INTERFACE WIRINGINSTALLATION NOTESCSB CUSTOMER INTERFACEX---SLOT 2 RIBBON CONNECTORX--

Strany 104

DESCRIPTION:DATE:DRAWING NO:4of5SHEET:REVISION:G051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 2 2Powerware 9330 (10 kVA--40 kVA)

Strany 105

DESCRIPTION:DATE:DRAWING NO:5of5SHEET:REVISION:G051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 2 3Powerware 9330 (10 kVA--40 kVA)

Strany 106 - 8.3.4 Setup Menu Screens

DESCRIPTION:DATE:DRAWING NO:1of2SHEET:REVISION:G061502PHYSICAL FEATURES AND REQUIREMENTS164201300---3A --- 2 4Powerware 9330 (10 kVA--40 kVA) Installa

Strany 107 - 16 MAY 2000 09 42 YES

DESCRIPTION:DATE:DRAWING NO:2of2SHEET:REVISION:G061502PHYSICAL FEATURES AND REQUIREMENTS164201300---3A --- 2 5Powerware 9330 (10 kVA--40 kVA) Installa

Strany 108 - SERIAL PORTS

A --- 2 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO:TYPICAL UPS SYSTEMSHEET:REVISION

Strany 109

A --- 2 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO:TYPICAL UPS SYSTEMSHEET:REVISION

Strany 110 - 8.4 System Controls Screen

DESCRIPTION:DATE:DRAWING NO:1of2UPS SYSTEM CONFIGURATIONSSHEET:REVISION:F164201300---5111501NOTE 2: Output Voltage must match BypassInput Voltage.NOTE

Strany 111

DESCRIPTION:DATE:DRAWING NO:2of2UPS SYSTEM CONFIGURATIONSSHEET:REVISION:F164201300---5111501NOTE 2: Output Voltage must match BypassInput Voltage.NOTE

Strany 112 - 8.4.1 Charger Controls Screen

iiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502-------------------------------------------------------------------

Strany 113 - 8.5 Unit Shutdown Screen

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 114

A --- 3 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GONELINE DRAWING

Strany 115 - UPS Operating Instructions

A --- 3 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:FOPTIONS CABINET

Strany 116

A --- 3 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of10111501UPS

Strany 117

A --- 3 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F3of10111501UPS

Strany 118 - 9.5 Cold Starting the UPS

A --- 3 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F4of10111501INBY

Strany 119

A --- 3 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F5of10111501UPS

Strany 120

A --- 3 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F6of10111501UPS

Strany 121 - Shutdown

A --- 3 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F7of10111501UPS

Strany 122

A --- 3 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F8of10111501UPS

Strany 123 - 9.16.1 To Use the REPO Switch

A --- 3 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F9of10111501INBY

Strany 124

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 1nGetting Started1.1 Installing the UPSThe cabinet sections of th

Strany 125 - Using Features

A --- 4 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F10 of 10111501U

Strany 126 - HORN SILENCE

A --- 4 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F1of511150116420

Strany 127

A --- 4 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of5111501UPS C

Strany 128

A --- 4 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F3of5111501UPS C

Strany 129 - Responding to System Events

A --- 4 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F4of5111501LOCAT

Strany 130 - 11.4 System Event Messages

A --- 4 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F5of5111501LOCAT

Strany 131

A --- 4 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of605300116420

Strany 132

A --- 4 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of6053001UPS C

Strany 133

A --- 4 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D3of6053001UPS C

Strany 134

A --- 4 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of6053001LOCAT

Strany 135

1-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The basic environmental requirements for operation of the UPS sy

Strany 136

A --- 5 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D5of6053001LOCAT

Strany 137

A --- 5 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D6of6053001LOCAT

Strany 138

A --- 5 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Strany 139 - Communications

A --- 5 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GLOCATION OF OPT

Strany 140 - SERIAL PORT (DB--9)

A --- 5 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Strany 141 - 12.5 Terminal Mode

A --- 5 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of4053001CONDU

Strany 142

A --- 5 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Strany 143 - Figure 12 ---6. Load Off

A --- 5 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GLOCATION OF OPT

Strany 144

A --- 5 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Strany 145 - Figure 12---10. Output Meter

A --- 5 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of4053001LOCAT

Strany 146 - Figure 12---11. Bypass Meter

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 31.1.5 Inspecting and Unpacking Each CabinetThe first task in pre

Strany 147 - Figure 12---13. Setup

A --- 6 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:FLOCATION OF BA

Strany 148

A --- 6 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Strany 149 - Figure 12 ---17. Versions

A --- 6 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of2111501UPS C

Strany 150 - 12.5.2 Event History Log

A --- 6 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Strany 151 - Display Version 0.96

A --- 6 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Strany 152

A --- 6 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D3of4053001UPS C

Strany 153 - Remote Notification

A --- 6 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:E4of4071501UPS C

Strany 154

A --- 6 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of2053001OPTIO

Strany 155 - 13.3 Description of Operation

A --- 6 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of2053001OPTIO

Strany 156 - 13.3.3 Housekeeping

A --- 6 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of2053001OPTIO

Strany 157 - 13.4 Hardware Requirements

1-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 1 ---2. Powerware 9330 (25 kVA ---40 kVA) UPS Cabinet as

Strany 158 - 13.5 Configuring the Modem

A --- 7 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of2053001OPTIO

Strany 159

A --- 7 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of1053001BATTE

Strany 160 - 13.6 UPS Se tup Configuration

A --- 7 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G164201300---181

Strany 161 - 13.6.1 Default Events

A --- 7 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G2of2051502REMOT

Strany 162

A --- 7 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G164201300---191

Strany 163 - Maintaining the UPS System

W--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502LIMITED FACTORY WARRANTY FOR THREE -PHASE POWERWARE PRODUCTSThis

Strany 164

W--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 165

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 53. Set each pallet on a firm, level surface, allowing a minimum

Strany 166 - 14.4 Maintenance Training

1-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 167 - Product Specificat i ons

2-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing the UPS System2.1 Preliminary Installation Informatio

Strany 168 - 15.3 UPS System Output

2-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2 UPS Cabinet InstallationTo install an UPS cabinet, perform t

Strany 169

2-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502VENTEDFRONTPANELSOLIDFRONTPANELFRONTSHIPPINGBRACKET (3)PALLETSHI

Strany 170

iiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Table of ContentsIntroduction xiii...

Strany 171

2-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502REARSHIPPINGBRACKET (3)PALLETSKID BOLTS (4)(3 PLACES)REMOVABLESK

Strany 172 - Po werw are 9330---20/10

2-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028. Remove three bolts, (2) in Figure 2---1, securing front shipp

Strany 173

2-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502FRONT VIEWSOLIDFRONTPANELFRONTSHIPPINGBRACKET (3)PALLETSHIPPINGB

Strany 174

2-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502REAR VIEWREARSHIPPINGBRACKET (3)PALLETSKID BOLTS (4)(4 PLACES)RE

Strany 175

2-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615024. Remove four bolts, (1) in Figure 2---4, securing the rear shi

Strany 176

2-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.3 Installing Optional Remote Battery Power Wiring to thePowe

Strany 177

2-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.4 Installing Optional Remote Battery Power Wiring to thePow

Strany 178

2-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.5 Installing UPS External Power Wiring1. Remove left front

Strany 179

2-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.6 Installing Customer ConnectionsNOTE: If installing connec

Strany 180

2-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.3 Battery Cabinet InstallationTo install optional battery cab

Strany 181

ivPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.5 Initial Startup 2---28...

Strany 182

2-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---5. Battery Cabinet Installation ---

Strany 183

2-- 15Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---6. Battery Cabinet Installation ---

Strany 184

2-- 16Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---7. Battery Cabinet Installation ---

Strany 185

2-- 17Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---8. Battery Cabinet Installation ---

Strany 186

2-- 18Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214. Install s ide panel removed from the UPS cabinet to the rig

Strany 187

2-- 19Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028. If permanently mounting the system, proceed to step 15; othe

Strany 188

2-- 20Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4 Options Cabinet Installation2.4.1 Unloading the Options Cab

Strany 189 - 5 amp minimum

2-- 21Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---9. Options Cabinet Installation --- Powerware 9330 (

Strany 190 - CSB CUSTOMER INTERFACE

2-- 22Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---10. Options Cabinet Installation --- Powerware 9330

Strany 191

2-- 23Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---11. Options Cabinet Installation --- Powerware 9330

Strany 192 - CONTACT RATING:

vPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027 Operational Controls and Features 7---1...7.1

Strany 193 - Table Z Remote EPO

2-- 24Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---12. Options Cabinet Installation --- Powerware 9330

Strany 194

2-- 25Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213. Remove the top side panel mounting screw (tie/grounding bra

Strany 195 - During Full Load Operation

2-- 26Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4.3 Installing Options Cabinet Internal Power Wiring1. Remove

Strany 196 - 164201300---4 1 of 2

2-- 27Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4.4 Installing Options Cabinet External Power WiringNOTE: Rem

Strany 197 - 164201300---4

2-- 28Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTE: Remove Options cabinet PDM conduit landing plate to punch

Strany 198

2-- 29Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.6.1 Installation Checklist-All packing materials and restrain

Strany 199

2-- 30Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Notes__________________________________________________________

Strany 200

3-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing and Connecting Batteries3.1 Important Safety Instruct

Strany 201 - 164201300---7

3-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.2 Battery TypeThe following battery types are supplied in the

Strany 202 - A --- 3 2

3-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 3---1. Battery Schematic --- Powerware 9330 (10 kVA ---20

Strany 203 - A --- 3 3

viPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029 UPS Operating Instructions 9---1...9

Strany 204 - A --- 3 4

3-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 3---2. Battery Schematic --- Powerware 9330 (25 kVA ---40

Strany 205 - A --- 3 5

3-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.3.2 Installing Internal Batteries in the Battery CabinetIf the

Strany 206 - A --- 3 6

3-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023. Remove screws securing internal safety shield panels and remo

Strany 207 - A --- 3 7

3-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTRED TOBLACKREDBLACKCONNECTRED TOBLACKCONNECTORCONN

Strany 208 - A --- 3 8

3-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.5 Installing and Connecting Re mote BatterySystemInstall and c

Strany 209 - A --- 3 9

4-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing a Remote EmergencyPower Off (EPO) Control4.1 Installa

Strany 210 - 10 of 10

4-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502TB2TB1COVERBOTTOM ENCL OSUREFigure 4---2. Remote EPO Control (in

Strany 211 - FRONT VIEW

4-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Table 4---1. Remote EPO Wire TerminationsFrom RemoteEPO Switch(s

Strany 212 - FRONT VIEW DETAIL

4-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 213 - LEFT VIEW

5-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing a RemoteMonitor Panel5.1 Installation ProceduresAs an

Strany 214

viiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213 Remote Notification 13---1...1

Strany 215 - TOP VIEW

5-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615025.2 To i n s t a l l a n R M P :NOTE: 1. Before installing an RM

Strany 216

5-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502PLUG-IN TERMINALTO REMOTE MONITORCABLE EXITFOR1/2” CONDUITOPENIN

Strany 217 - POWER TERMINALS

5-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 218

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Section IIOperation

Strany 219

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 220

6-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Understanding UPSOperation6.1 Looking Inside the UPS SystemThe P

Strany 221 - X4 X3 X2 X1

6-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DIGITALAC INPUT TOAC INPUT TOAC OUTPUTINPUTRECTIFIERINVERTERFILT

Strany 222

6-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2 UPS ModesThe UPS system functions automatically to supply AC

Strany 223 - (SEE SHEET 3 FOR DETAILS)

6-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.1 Normal ModeFigure 6---2 shows the path of electrical power

Strany 224

6-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The battery charger derives its input from the unregulated DC ou

Strany 225

viiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502List of FiguresFigure 1---1. Powerware 9330 (10 kVA---20 kVA)Cabi

Strany 226

6-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.2 Bypass ModeThe U PS automatically switches to Bypass mode

Strany 227 - NEUTRAL TERMINALS

6-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502the inverter rectifier. The static switch being an electronicall

Strany 228 - DESIGNATION

6-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.3 High Efficiency ModeWhen the UPS is operating in High Effi

Strany 229

6-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.4 Battery ModeThe U PS transfers to Battery mode automatical

Strany 230 - BATTERY CABINET TERMINALS

6-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502If the input power fails to return or is not within the accepta

Strany 231

6-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.5 Test and Maintenance Bypass ModesAn internal maintenance

Strany 232

6-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CB1CB2K1K5K3K2OpenClosedBreakersContactorsMain Power FlowEnergi

Strany 233

6-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.3.2 Boost Converter and Neutral RegulatorA Boost Converter co

Strany 234

6-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 235

7-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Operational Controlsand Features7.1 GeneralThe UPS system should

Strany 236

ixPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 6 --- 1 . M a i n E l e m e n t s o f t h e U P S S y s

Strany 237 - OPTIONS CABINET

7-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CONTROLPANELAC INP UTBREAKERBATTERYBREAKER CB2BYPASSBREAKERBATTE

Strany 238

7-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CONTROLPANELBATTERYBREAKERUPSCABINETAC INP UTBREAKER CB1COLDSTAR

Strany 239

7-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.2.2 UPS Circuit BreakersThe UPS can contain as many as 10 circ

Strany 240

7-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Summary Alarm ContactsAlarm contacts are provided for connection

Strany 241 - BATTERY CABINET

7-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.4.2 Remote Monitor PanelAn optional Remote Monitor Panel (RMP)

Strany 242 - 164201300---18

7-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.4.6 CommunicationsModemAn optional modem is available for use

Strany 243

7-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.5 Safety ConsiderationsThe UPS enclosure is designed for indus

Strany 244

7-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.6 Symbols, Controls, and IndicatorsThese symbols may appear on

Strany 245

7-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Strany 246

8-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Using the Control Panel8.1 DescriptionThis chapter describes the